How the battery round-trip efficiency calculation works
- Measure from the same state of charge, for example full to 20% and back to full, so the battery ends where it started.
- Most inverters and battery monitors log energy in and out; a shunt-based monitor gives the most accurate figures.
- Efficiency falling over time can be a sign of ageing cells or rising internal resistance.
Frequently asked questions
What is a good round-trip efficiency?
+
Above 90% is normal for lithium batteries. 80–85% is typical for lead-acid. Below 75% suggests a problem such as heat, ageing or a parasitic load.
Does round-trip efficiency include the inverter?
+
It depends where you measure. Measured at the battery terminals it is battery-only; measured at the AC side it includes inverter and charger losses, typically 85–90% overall.
Why is one-way efficiency the square root?
+
Losses happen on both the way in and the way out. If they are roughly equal, each direction has an efficiency equal to the square root of the round trip.
Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.