Undersized cables waste energy as heat and can be a fire risk, especially at the high currents of 12V and 24V systems. Enter your current, cable run and voltage to get the minimum wire gauge that meets both voltage drop and ampacity limits.

THELOADCALCWR-01 · Wiring & Safety unit
Minimum wire sizeWR-01
4 AWG
Metric equivalent16 mm²
Required area14.33mm²
Actual voltage drop2.03%
Wire ampacity (75°C)85A
Sized for both voltage drop and 125% continuous current
Current
One-way cable length
Length units
System voltage
Max voltage drop
3.0%
Conductor

How the solar wire size calculation works

Min area (mm²) = 2 × Length × Current × ρ ÷ (Voltage × Max drop)
ρ = 0.0172 Ω·mm²/m (copper), 0.0282 (aluminum)
  • Length is the one-way distance; the formula doubles it because current flows out and back.
  • The chosen wire must also carry 125% of the current continuously, using 75°C copper ampacity from NEC Table 310.16.
  • Aim for 3% drop or less on most DC circuits, and 1–2% on battery-to-inverter cables.

Frequently asked questions

What size wire do I need for 30 amps at 12V over 5 meters?

+

For 3% voltage drop you need at least 14.3 mm², so 4 AWG copper (or 16 mm² metric).

Why do low-voltage systems need thick cables?

+

For the same power, 12V carries four times the current of 48V. Voltage drop and heat rise with current, so low-voltage cables must be much thicker.

What wire is best for solar panels?

+

Use UV-resistant, sunlight-rated PV wire or USE-2 for exposed array wiring, typically 10 or 12 AWG for panel strings.

Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.