How the grounding rod calculation works
- Soil resistivity ranges from about 10 Ω·m in wet organic soil to over 1,000 Ω·m in dry sand or rock.
- NEC 250.53 requires a single rod to measure 25 Ω or less; otherwise, add a supplemental rod at least 6 ft away. Most installers simply drive two rods.
- Rods spaced at least twice their length apart interact least. Spacing closer than that reduces the benefit of the second rod.
Frequently asked questions
How many ground rods do I need for solar?
+
Typically two, spaced at least 6 ft apart, unless a single rod is tested at 25 Ω or less. In poor soil you may need more, or a ground ring.
Does a thicker ground rod lower resistance?
+
Only slightly. Going from 5/8" to 3/4" changes resistance by just a few percent. A longer rod helps much more.
What is the resistance of an 8 ft ground rod?
+
In loamy soil of about 100 Ω·m, roughly 40 Ω, which is why a second rod is usually needed.
Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.