Grounding Rod Calculator

A solar system's grounding electrode needs low resistance to earth. Soil type matters far more than the rod itself. Choose your soil and rod to estimate resistance and how many rods it takes to meet the NEC 25-ohm benchmark.

THELOADCALCWR-06 · Wiring & Safety unit
Single-rod resistanceWR-06
39.9Ω
Rods for ≤ 25 Ω2pcs
Two rods (NEC default)22.9Ω
Min. rod spacing16ft
Add a supplemental rod at least 6 ft away (NEC 250.53(A)(2))
Soil type
Rod length
Rod diameter

How the grounding rod calculation works

Dwight: R = ρ ÷ (2πL) × (ln(4L ÷ a) − 1)
ρ = soil resistivity (Ω·m), L = rod length (m), a = rod radius (m)
  • Soil resistivity ranges from about 10 Ω·m in wet organic soil to over 1,000 Ω·m in dry sand or rock.
  • NEC 250.53 requires a single rod to measure 25 Ω or less; otherwise, add a supplemental rod at least 6 ft away. Most installers simply drive two rods.
  • Rods spaced at least twice their length apart interact least. Spacing closer than that reduces the benefit of the second rod.

Frequently asked questions

How many ground rods do I need for solar?

+

Typically two, spaced at least 6 ft apart, unless a single rod is tested at 25 Ω or less. In poor soil you may need more, or a ground ring.

Does a thicker ground rod lower resistance?

+

Only slightly. Going from 5/8" to 3/4" changes resistance by just a few percent. A longer rod helps much more.

What is the resistance of an 8 ft ground rod?

+

In loamy soil of about 100 Ω·m, roughly 40 Ω, which is why a second rod is usually needed.