Breakers protect your wiring from overcurrent. Choose the circuit type and enter its current to get the minimum breaker rating, rounded up to a standard size, along with the smallest copper wire that rating can protect.

THELOADCALCWR-04 · Wiring & Safety unit
Breaker ratingWR-04
45A
Max circuit current34.5A
Minimum OCPD43.1A
Min. copper wire8 AWG
Use a DC-rated breaker at or above system voltage
Circuit
Isc (PV) or max continuous current
Parallel strings (PV only)

How the solar breaker size calculation works

PV circuit: Breaker ≥ Isc × Strings × 1.25 × 1.25 (= 1.56)
DC / AC circuits: Breaker ≥ Continuous current × 1.25
  • NEC 690.8 treats PV current as continuous and allows for sunlight above standard test conditions, giving the 1.56 factor.
  • Breakers are rounded up to the next standard rating from NEC 240.6.
  • Use DC-rated breakers on DC circuits. AC breakers cannot reliably interrupt DC arcs.

Frequently asked questions

What size breaker do I need between solar panels and charge controller?

+

For two parallel strings with 13.8A Isc, the minimum is 43A, so a 45A DC breaker, with wire rated at least 45A (8 AWG copper).

Why multiply by 1.25 twice for solar?

+

Once because panels can exceed their rated current in bright sun, and once because the circuit carries current continuously for 3+ hours.

Can a breaker be bigger than the wire rating?

+

No. The breaker protects the wire, so the wire's ampacity must be at least the breaker rating.

Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.