Solar Fuse Size Calculator

When three or more solar strings are wired in parallel, a fault in one string can draw current from all the others. String fuses prevent that. Enter your panel Isc and string count to get the correct fuse size.

THELOADCALCWR-05 · Wiring & Safety unit
String fuseWR-05
25A
Minimum (1.56 × Isc)21.5A
Module limit25A
Combiner output current51.8A
Fuses needed3pcs
Fuse each string (both conductors if ungrounded)
Panel / string Isc
Parallel strings
Module max series fuse

How the solar fuse size calculation works

Minimum fuse = Isc × 1.56
Fuse ≤ Module maximum series fuse rating
Fuses required when parallel strings ≥ 3
  • With one or two strings, the reverse current from the other string cannot exceed what a panel is rated to withstand, so fuses are usually not required.
  • With three or more strings, each string needs a fuse sized between 1.56 × Isc and the module's maximum series fuse rating.
  • Use gPV-rated fuses designed for DC solar circuits, in a combiner box.

Frequently asked questions

Do I need fuses for my solar panels?

+

Only when three or more strings are connected in parallel. With one or two strings, fusing is generally not required by NEC 690.9.

What fuse size for a 13.8A Isc panel?

+

At least 21.5A, so a 25A fuse, provided the panel's maximum series fuse rating is 25A or higher.

What is the maximum series fuse rating?

+

The largest fuse the panel manufacturer allows in series with the module, printed on the datasheet. It protects the panel from reverse current.

Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.