IN-08Inverters

Inverter to Battery Matching Calculator

An inverter is only as good as the battery feeding it. Enter your inverter rating, typical load and runtime to get the battery capacity, the peak DC current, and the fuse, cable and BMS ratings needed to handle it safely.

THELOADCALCIN-08 · Inverters unit
Battery capacity neededIN-08
309Ah
Max DC current139A
Fuse / breaker175A
Min. cable2/0 AWG
Min. BMS rating139A
Keep battery cables short to limit voltage drop
Inverter rating
Typical load
Runtime wanted
Battery voltage
Chemistry

How the inverter to battery matching calculation works

Max DC A = Inverter W ÷ Battery V ÷ 0.9
Battery Ah = Load W × Hours ÷ (V × 0.9 × DoD)
Fuse ≥ 1.25 × Max DC A
  • At full output a 3,000W inverter on 12V draws over 270A, which is why larger inverters belong on 24V or 48V batteries.
  • The battery's BMS must allow at least the inverter's maximum DC current, or it will shut down under heavy loads.
  • Cable gauge here uses 75°C copper ampacity; keep battery-to-inverter runs as short as possible.

Frequently asked questions

What battery do I need for a 3000W inverter?

+

On 24V, the battery must supply about 140A at full load. For 1,200W for 5 hours you need roughly 310Ah of LiFePO4 at 24V.

What size fuse do I need between battery and inverter?

+

At least 125% of the maximum DC current, rounded up to a standard size: a 175A fuse for a 3,000W, 24V inverter.

Can I run a 3000W inverter on a 100Ah battery?

+

Only briefly. At full power a 12V 100Ah battery would last under 20 minutes and most 100Ah BMSs cannot supply 270A.

Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.