How the solar array (panel) sizing calculation works
Array W = Daily Wh ÷ (Peak sun hours × (1 − Losses))
Panels = ⌈Array W ÷ Panel W⌉
- For grid-tied systems use annual average sun hours. For off-grid systems use your worst month so you are covered in winter.
- Losses of 15–25% cover temperature, wiring, inverter and, for off-grid, battery charging losses.
- Allow about 2 m² (21 ft²) of roof or ground per 400W panel including gaps.
Frequently asked questions
How many solar panels do I need for 5 kWh per day?
+
With 4.5 peak sun hours and 20% losses you need about 1.4 kW, or four 400W panels.
How many panels to power a house?
+
An average US home using 29 kWh per day needs roughly 7–9 kW, or 18–23 panels of 400W, depending on location.
Should I add extra panels?
+
For off-grid, 10–25% extra panels help recharge batteries faster after cloudy days. Panels are cheap compared with batteries.
Results are engineering estimates for planning. Confirm final designs against equipment datasheets and local electrical codes, and have high-voltage or grid-connected work checked by a licensed electrician.